FiremeshBlog

Who Is Actually Responsible When a Sprinkler System Fails?

Written by Tahani Berge | Apr 28, 2026 9:08:26 PM

Most people assume it's a technical fault. The law says it's the building owner's fault.

The Short Answer

As a building owner, you are legally responsible for ensuring your sprinkler system is inspected and operational at all times. Installing the system is not enough. Having it inspected two years ago is not enough. The responsibility is ongoing — and it rests with you, regardless of who you have contracted to do the work.

This is not a question of insurance. It is a question of law.

What the Regulations Actually Say — One Level Deeper

The Legal Framework You Cannot Avoid

Sprinkler systems in Norway are governed by a hierarchy of legislation that makes one thing clear: the owner is responsible.

The Fire and Explosion Prevention Act, Section 6 requires owners to "keep safety devices in proper condition and ensure that they function as intended at all times."

The Fire Prevention Regulation, Section 5 specifies that building owners must ensure that installations designed to detect or limit fire "are inspected and maintained so that they function as intended."

Section 9 adds that owners must have routines for detecting, correcting, and preventing deficiencies — not merely reacting to them.

Owners may delegate the practical work to a tenant, property manager or external contractor. But the responsibility cannot be delegated. If something fails, your name is still on the paperwork.

What Is the Difference Between Inspection, Control and Maintenance?

These three terms are often used interchangeably, but regulations draw a clear distinction:

Term Who Performs It? What Does It Involve?
Inspection Owner or manager Simple self-check — look and verify everything appears correct
Control Qualified personnel Systematic review against requirement documents and standards
Maintenance Certified technician Servicing, repairs and remediation of documented deficiencies
Source: Fire Prevention Regulation with guidance, DSB (Norwegian Directorate for Civil Protection). All three are necessary. None of them can replace the others.

What NS-EN 12845 Requires — Week by Week

NS-EN 12845:2015 is the standard all Norwegian sprinkler systems must comply with. It does not just set goals — it sets minimum intervals.

Every 7 days — mandatory

Weekly Inspection

  • Check and log all water and air pressure gauges
  • Verify that the main stop valve is in the correct position
  • Test water alarms for a minimum of 30 seconds
  • Test that fire pumps start automatically
  • Check fuel and oil levels
  • Inspect for leaks of fuel, coolant or exhaust
Every month

Monthly Inspection

  • Check lead-acid battery cells
  • Inspect the diesel pump's start battery
  • Check control panel batteries
  • Replace batteries with low cell voltage
Every 3 years

Backflow Preventer Service

  • All stop valves, alarms and backflow preventers must be inspected and replaced if necessary (NS-EN 12845 § 20.3.5.3)
Every year

Third-Party Inspection

  • Independent party issues a formal inspection report
  • Report assesses compliance with NS-EN 12845:2015
  • All deficiencies must be listed and documented

What Is Missing From Today's System

The rules are clear. The practice is something else.

A report from the Information Office for Automatic Extinguishing Systems (OFAS) reviewed 150 randomly selected Norwegian sprinkler systems and found that 33% had not carried out any inspection at all — not just missing some checks, but no inspection whatsoever.

The reason? "Neither insurers nor supervisory authorities are able to enforce the correction of faults in the systems." (OFAS, 2003)

In Denmark, systems lose their approval if serious faults are not corrected within a set deadline. In Norway, no equivalent mechanism exists. The consequences of non-compliance are effectively absent — until there is a fire.

Log-Keeping: The Part Most People Forget

NS-EN 12845 requires that a log of all inspections be maintained and kept on the premises. The user must appoint a responsible person — with a designated deputy — who, after training, ensures the system is in working order.

A log that does not exist is not just a breach of the standard. It is a legal exposure. If a fire occurs and it cannot be documented that inspections were carried out, the insurer has grounds to reduce or deny a claim.

How Firemesh Solves This in Practice

Firemesh was developed to fill exactly this gap — between what regulations require and what actually happens in practice.

The system continuously and automatically monitors the critical checkpoints in NS-EN 12845:

  • No forgotten inspections — the system performs them without human intervention
  • Automatic logging — everything is documented digitally, available for audit
  • Immediate alerts — if anything deviates, the responsible person is notified instantly
  • Insurance integration — the system can notify the insurer if deficiencies are not followed up

Regulations set the requirements. Firemesh ensures they are actually met.

→ See how Firemesh works in your building

Frequently Asked Questions

Who is responsible if the sprinkler system fails during a fire?

The building owner is legally responsible. Responsibility cannot be transferred to a property manager, tenant or contractor, even if those parties carry out the practical inspections.

What is the difference between an inspection and a control?

An inspection is a simple self-check carried out by the owner or manager. A control is a more systematic review performed by qualified personnel. Both are required — neither can substitute for the other.

How often must sprinkler systems be inspected?

Weekly inspection is the minimum requirement under NS-EN 12845. Monthly control, three-yearly servicing of backflow preventers and annual third-party inspection are also required.

What happens if no inspection log has been kept?

Absent documentation undermines the ability to prove that maintenance was carried out. This can provide grounds for insurance reduction and is itself a breach of NS-EN 12845.

Can an automated system count as inspection under NS-EN 12845?

It depends on which checkpoints the system covers and whether the documentation meets the standard's requirements. Firemesh is built specifically around these functional requirements.

Are the requirements in Norway the same as elsewhere in Europe?

NS-EN 12845 is a European standard that applies across the EEA. The requirements are the same — but the sanctions regime for non-compliance varies significantly between countries.

Source: RISE Fire Research, report A19 20412:1 "Requirements for inspection and reliability of sprinkler systems", 2019. Commissioned by Firemesh AS.